SELF LIMITING CABLE – High Temperature 60 W/M

Regulating Tracer suited for high temperature applications for tanks & pipeline

 

  • High temperature applications
  • Can with stand temperatures associated with steam purging operations
  • Fluoropolymer jacket providing electrical insulation, mechanical strength & moisture resistance
  • UV resistant Fluoropolymer to enable usage in corrosive area & High temperatures.

 

It is suitable for maintaining temperatures up to 180°C These tracers can withstand temperatures associated with steam purging operations in the pipelines.

 

APPLICATION

  • Tanks
  • Pipelines

 

CONSTRUCTION

The cable consists of a self-regulating parallel circuit of a semi-conductive heating core extruded over plated copper bus wires.
Modified Polyolefin insulation over semi-conductive heating core provides electrical insulation, over which an Aluminum tape with earth drain wire metal sheathing is provided for earthing.
An outer sheath of Modified Polyolefin makes the heating cable robust and waterproof.

  1. 3.3 Sq.mm Nickel Plated Copper.
  2. Fluoropolymer Insulation.
  3. Coiled Alloy Heating Element.
  4. Fiber Glass braid.
  5. Fluoropolymer Jacket providing electrical insulation, mechanical strength & moisture resistance.
  6. Coated copper braid to give a continuous ground path.
  7. Outer Jacket UV resistant Fluoropolymer to enable usage in corrosive area & High temperatures.

 

SPECIFICATIONS

  • Compliance Standards – EN 60079-0, IS/ IEC / EN 60079-30-1 & EN 60079-31
  • Approvals – TI (ATEX) for Zone I / Division II & EAC for use in hazardous area applications
  • Safety – As the Cable self regulates its heat output, its limit the maximum sheath temperature, thus making it burnout proof.
  • Compliance Standards – EN 60079-0, IS/ IEC / EN 60079-30-1 & EN 60079-31 
  • Heating Power W/m (230V AC) at 10 C – 60 W/M
  • Voltage Supply  – 230/240VAC, 50/60 Hz, 110/120VAC, Max. 500V on request
  • Max. Installation Temperature Power On – 150℃
  • Max. Exposure Temperature Power Off – 260℃
  • Min. Installation Temperature – -65℃
  • Minimum Bending Radius – 25mm

60 W/M

SELF LIMITING CABLE – High Temperature 60 W/M

Datasheet

Send an inquiry

We consistently strive to develop serious and long-term cooperative relationships with our partners and suppliers.

Contact us

Are you interested in a collaboration?

We consistently strive to develop & build serious and long-term cooperative partnerships with our partners and suppliers.

Call me
Download
E-catalogue